Product Description
12 Volts, 12 Amp-Hours
Connectors and Fuse Included
Meets or exceeds the original manufacturers specifications.
Weight: 10lbs.
Chemistry: Sealed Lead Acid
Dimensions: 5.95 x 4.00 x 3.75
Weight: 8.90 lbs
Terminals: F2 or .250'' Tabs
Warranty: 12 MONTHS
Charging
Standby use: Apply constant voltage charging at 2.275 volts per cell (or 2.25-2.30VPC).
Cyclic use: Apply constant voltage charging at 2.40-2.50 VPC.
Initial charging current should be set at less than 0.25CA.
Top charge: Product in storage (ambient temperature 25°C/77°) requires a top charge every six months. Apply constant voltage at 2.40 volts per cell, initial charging current should be set at less than 0.1CA for 15 to 20 hours.
Discharge
Stop operation when voltage has reached the minimum permissible voltae. Recharge immediately.
Do not operate at 6CA or more current continuously.
Storage
Always store battery in a fully charged condition.
If battery is to be stored for a long period, apply a recovery top-charge every 6 months.
Store batteries in a dry and cool location.
Temperature
Keep within ambient temperatures of –150C to +500C for both charging and discharging.
Incorporating battery into equipment
Encase battery in a well ventilated compartment.
Avoid installing battery near heated units such as a transformer.
House the battery in the lowest section of the equipment enclosure or rack to prevent unnecessary battery temperature rise.
Other
Avoid terminal short circuit.
DO NOT expose to open flame.
Avoid setting batteries in environments which can cause direct contact to gasoline, paint thinner, organic solvents, synthetic resins, oil, etc.