Yuasa/Genesis NP0.8-12 12V/0.8AH Sealed Lead Acid Battery with WL-TH Terminal
Yuasa/Genesis NP0.8-12 12V/0.8AH Sealed Lead Acid Battery with WL-TH Terminal
Item ID
14058
Brand
YUASA
SRP
$29.99
Our Price
USD $21.84
Availability
In Stock
QTY:
Shipping Rate Calculator
State:
Country:
FedEx International Economy (Canada)
$31.82
Product Description
Yuasa/Genesis VRSLA batteries provide powerful solutions for the telecom, utility, electronic, switchgear, and any other industry requiring total power systems capabilities.
12 Volt, 0.8 Ah
WL-TH Terminal
High quality lead insures maximum performance
Dimensions: Length: 3.78 x Widith: 0.98 x Height: 2.42"
Charging
Standby use: Apply constant voltage charging at 2.275 volts per cell (or 2.25-2.30VPC).
Cyclic use: Apply constant voltage charging at 2.40-2.50 VPC.
Initial charging current should be set at less than 0.25CA.
Top charge: Product in storage (ambient temperature 25°C/77°) requires a top charge every six months. Apply constant voltage at 2.40 volts per cell, initial charging current should be set at less than 0.1CA for 15 to 20 hours.
Discharge
Stop operation when voltage has reached the minimum permissible voltae. Recharge immediately.
Do not operate at 6CA or more current continuously.
Storage
Always store battery in a fully charged condition.
If battery is to be stored for a long period, apply a recovery top-charge every 6 months.
Store batteries in a dry and cool location.
Temperature
Keep within ambient temperatures of –150C to +500C for both charging and discharging.
Incorporating battery into equipment
Encase battery in a well ventilated compartment.
Avoid installing battery near heated units such as a transformer.
House the battery in the lowest section of the equipment enclosure or rack to prevent unnecessary battery temperature rise.
Other
Avoid terminal short circuit.
DO NOT expose to open flame.
Avoid setting batteries in environments which can cause direct contact to gasoline, paint thinner, organic solvents, synthetic resins, oil, etc.